Rosemount 3051S

25

Hazardous Locations Certifications

North American Certifications

FM Approvals
E5

Explosion proof for Class I, Division 1, Groups B, C, and D;
dust-ignition proof for Class II and Class III, Division 1, Groups E,
F, and G; hazardous locations; enclosure Type 4X, conduit seal
not required when installed according to Rosemount drawing
03151-1003.

I5

Intrinsically Safe for use in Class I, Division 1, Groups A, B, C,
and D; Class II, Division 1, Groups E, F, and G; Class III, Division
1; Class I, Zone 0 AEx ia IIC when connected in accordance with
Rosemount drawing 03151-1006; Non-incendive for Class I,
Division 2, Groups A, B, C, and D, Enclosure Type 4X
For entity parameters see control drawing 03151-1006.

Canadian Standards Association (CSA)
E6

Explosion-Proof for Class I, Division 1, Groups B, C, and D;
Dust-Ignition-Proof for Class II and Class III, Division 1, Groups
E, F, and G; suitable for Class I, Division 2, Groups A, B, C, and
D, when installed per Rosemount drawing 03151-1013, CSA
Enclosure Type 4X; conduit seal not required.

I6

Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D
when connected in accordance with Rosemount drawings
03151-1016;
For entity parameters see control drawing 03151-1016.