Maintenance/Troubleshooting

Operating instructions for blueplanet-gridsave eco_EN

Page 39

9.5.2 Troubleshooting

B = Action of the operator
E = The indicated work may only be carried out by an authorised electrician.
K = The indicated work may only be carried out by a service employee of KACO new energy GmbH.

Fault

Cause of fault

Explanation/remedy

By

All LEDs

are off

AC and

DC voltages not

present

"

Check whether the DC and AC voltages are within the per-

mitted limits. (see Technical Data)

E

"

Notify KACO Service.

E

Transfer display

not on

AC supply is out-

side the tolerance

range for synchro-

nisation.

Voltage or frequency is outside the specified limit values.

"

If the AC source is a generator, check whether or not it

requires maintenance.

B

"

If the AC source is the power grid, contact your grid opera-

tor to check if there is a problem.

E

Check both sources to ensure that the limit values are suitable.

E

"Generator fault“

alarm

Generator Fault

On the generator, there is no generator voltage present within

1 minute three times in succession following generator start or

the generator voltage is not synchronous within 5 minutes.

"

Device re-starts after 15 min, 1 hour and daily if a pre-pro-

grammed SoC level or if a limit value has been achieved for

low DC voltage.

"

Force the re-start of the device by pressing the "Generator"

key

E

The genera-

tor starts more

frequently

than normal or

expected

The average load

of the plant has

increased.

On the "Data View" tab of the "GS eco link", compare "AC Load

Energy" under "AC History" to the following values:

"

Check values that have been set with the plant installation.

E

"

Design specification for the plant that you should have

received from the installation engineer.

"

If the loads have been increased significantly, identify all

the devices added.

E

The peak load

of the plant has

increased

On the "Data View" tab of the "GS eco link", compare the

"Power" and "Power 5 min average" values in the "AC Source"

section:

"

Contact KACO Service to test the hardware.

E

"

On the "Generator Auto Run" tab, the settings should be

activated by the system integrator:

"On 5 minute load power" and

"On 15 minute load power"

K

Table 6:

Troubleshooting