Maintenance/Troubleshooting

Page 42

Operating instructions for blueplanet-gridsave eco_EN

Fault

Cause of fault

Explanation/remedy

By

Battery problems

The battery is not

being charged

corrrectly

Check that the battery charging requirements in the device are

correctly set.

• Check that the solar controller has been set correctly.
• Check all cables and connections to the batteries.
If it appears that the solar system is barely working at all, the

solar controller may be set too low. Check the displays and the

DC History in "GS eco link".

B

Perform a visual inspection on the battery and check for loose

connections. Monitor the battery voltage if high loads supplied

by the device are connected and disconnected.

• Check the voltage on each individual battery of the battery

to determine whether any cells are not fully charged or are not

absorbing any charge.

Measure the voltages on each cell / battery at different times

in the charge/discharge cycle: immediately after the start of

charging, for example, after about 10 minutes, in the middle

of the charging, immediately before the end of the charge, 10

minutes after the beginning of the discharge, in the middle

of the discharge and immediately before the end of the dis-

charge.

E

Problems with

solar-hybrid sys-

tems
(on-grid)

Main supply is

available but the

system is losing

power

Device is disconnected from the power supply due to high

voltage or frequency, so that the site is supplied via the limited

battery system.

"

Increase the "Sync Tolerance" parameters or contact the

grid operator..

E

The DC-connected

system is not

exporting the cur-

rent as expected.

Solar system (external device for gridsave eco restricts the cur-

rent flow from the solar module.

"

The nominal value for the trickle charge solar controller

must be approx. 1 V higher than the nominal value for the

trickle charge of the bidirectional battery inverter.

E

Problems with

starting or stop-

ping an off-grid

generator

"

In "GS eco link", open the "Generator Running Reason" area

on the "Now" tab in the "Data View" area

B

"

If the reason does not have anything to do with the actual

processes in the system, contact your installation engineer

or the KACO new-energy service hotline.

.

E

System is not

functioning cor-

rectly

"

Check the alarm displays on the control panel and in the

"GS eco link" software

B

"

Carry out the measure recommended in the "Attention

Required" field, in the "DataView – Now" area.

"

Switch the device to no-load by pressing the button for

several seconds and then switch back on again. If this does

not restore normal operation, look for a cause in the Perfor-

mance Data Events.

B

Table 6:

Troubleshooting