Installation, Figure 5, incorrect dc wiring – Magnum Energy Series Stacking Cable Kit (ME-SSI) User Manual

Page 11

Advertising
background image

©

2010 Magnum Energy, Inc.

Installation

6

Figure 5, Incorrect DC Wiring

6 volt

battery

6 volt

battery

6 volt

battery

6 volt

battery

6 volt

battery

6 volt

battery

6 volt

battery

6 volt

battery

This battery bank uses two battery strings . They must

be connected together in parallel to provide a single

battery bank to the inverters .

The battery bank

cables are going to

one inverter, this is

NOT RECOMMENDED

DC disconnect and

overcurrent protection

DC Positive and

Negative

Interconnects

(from ME-SSI kit)

MS4024

L1

inverter

MS4024

L2

inverter

INCORRECT WAY TO CONNECT THE BATTERY

BANK TO THE SERIES STACKED INVERTERS .

**DO NOT WIRE THIS WAY**

Stacker cable

(from ME-SSI kit)

Incorrect DC wiring – As shown in Figure 5, do not attempt

to connect the positive and negative to one inverter and then

jumper the negative and positive to the second inverter. This will

not distribute the current into and out of the battery bank evenly

and may not allow the second inverter to receive suffi cient current

if powering a heavy load. If you have a single battery cable pair,

use Figure 3 to guide you in wiring your DC battery cables to the

stacked pair of inverters.