Operation

When two inverters are series stacked and inverting, they coor-

dinate with each other to ensure the output can power 240VAC

loads. This requires that the inverters turn on together and switch

to the AC source at the same time; and, both inverters should shut

down if either one becomes inoperable. This Operation section

provides a functional test to ensure the two inverters are working

together as a series stacked pair, and also provides information

pertinent to the set-up and operation of a series stacked confi gura-

tion.

Using the Remote Control

The default settings in your inverter are adequate for most

installations; however, in a series stacked confi guration we highly

recommend using the ME-RC50 or ME-ARC50 remote controls.

These remote controls can be used to monitor the inverter’s status

and make set-up changes. A single remote can be used to confi g-

ure each inverter, but not at the same time. If you want the ability

to monitor and confi gure both units at the same time, each invert-

er will require its own remote.

Info: To use a remote control, it must have revision

1.2 or higher to work properly with a series stacked

confi guration.

Functional Test

Series stacked inverters must communicate together to provide

120/240VAC to the loads and shut down if any inverter faults oc-

cur. This functional test will confi rm the two units are operating

correctly as a series stacked pair. Before performing the functional

test, ensure the following:

All DC disconnects to the inverters are turned off.

All AC input and output circuit breakers are turned off.

Only the stacker cable provided in the ME-SSI is used.

The stacker cable is connected to each inverter’s Stack Port

(red label).

Only MS4024 inverter models are stacked together.

NEUT OUT of both inverters are connected to the same neutral

bus.

DC and AC grounds are both connected and properly installed.

AC input connections and AC output connections are wired

correctly on the terminal block and not reversed (double-check

before turn-on).

All DC connections are properly connected and tight.

Operation