Magnum Energy Series Stacking Cable Kit (ME-SSI) User Manual

Page 23

Advertising
background image

©

2010 Magnum Energy, Inc.

Operation

18

Inverter Operation

Invert Mode - The units are turned on by pressing the Power ON/

OFF switch on either inverter. Alternatively, they can also be start-

ed by pressing the INVERTER ON/OFF button on a remote control

connected to either inverter. When the two inverters are inverting,

they communicate over the Stacker cable. This cable communi-

cates to monitor the AC output from each inverter and shift it 180°

out of phase from each other to provide 240VAC on both units,

and to verify that there are no faults on either unit to prevent only

one unit from inverting. The two units also use the DC negatives

as a reference point while they are communicating; hence, the

reason why the DC negatives must be tied together – to ensure

there is no negative voltage difference between the two units.
Inverter settings - When the units are inverting as a series

stacked confi guration, certain settings must be coordinated in each

unit for proper operation. Without a remote control, the default

settings on each unit will be coordinated. If using a remote con-

trol, check that the following settings are the same between the

two units:
1. Ensure the Adj LowBatCutOut setting is the same for both units.
2. If the Search mode is needed, then set the Adj Search Watts

setting for each inverter to determine when to start powering

120VAC loads. The two inverters are independent, which means

one inverter can come out of Search mode and start inverting,

while the other unit continues in the Search mode until a load ex-

ceeds the search watts threshold of that unit. If powering 240VAC

loads, then the search watts sensibility is determined by combining

the ‘Search Watts’ setting on both units.
For example: Given a 15 watt Search Watts setting on the L1

inverter and a 10 watt Search Watts setting on the L2 inverter,

and a 20 watt/120VAC load on the L1 inverter and no load on the

L2 inverter. This would cause the L1 inverter to start inverting, but

the L2 inverter would continue in Search mode. With the same

Search Watts settings, a 25 watt/240VAC or greater load would

cause both the L1 and L2 inverters to come on and start inverting.

Charger Operation

Charge Mode – The series stacked confi guration is designed to

accept 120VAC to each inverter, typically from a split-phase, 3 wire

120/240VAC power source. The HOT IN terminals of each inverter

accepts one line of 120VAC each and the NEUT IN terminals of

both inverters are tied together and connected to the AC power

source neutral line. When the AC line voltage and frequency are

good to both units, they both transfer and go to Charge mode and

begin charging – if enabled. However, it is not necessary for either

unit to have charging enabled for the pair to operate.