1 using the lcd screen – Eaton Electrical Powerware 9315 User Manual

Page 28

Advertising
background image

Using the Monitor Panel

5-2

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

5.1 Using the LCD Screen

The LCD screen at the top of the Monitor Panel provides an operator interface with the

UPS. Figure 5-2 identifies the display fields discussed in the following sections.

Uninterruptible Power System

System Normal

Alarm:

None

Notice: None

Meters

System

Load Amps

Events Statistics Graphics Setup

Input

Output

Bypass

Battery

VAB

480

VBC

VCA

KW

379

KVA

399

IA

IB

IC

FREQ

60.0

PF

0.95

V

540

I

000

Meters

480

480

480

480

480

VAB

480

VBC

VCA

480

480

IA

IB

IC

361

361

361

IN

000

VAB

480

VBC

VCA

480

480

FREQ

60.0

KVA

300

KW

240

PF

0.80

Battery

04 MAY 1997

14:23:45

100%

Percent

B

C
D

E

A

F

G

Figure 5-2. Parts of the LCD Screen (Typical for Powerware 9315 300 480/480V UPS)

A

The UPS status area contains three lines that display the current state of the UPS. The first line

shows the present operational mode of the UPS. The second line shows the highest level of the

current active alarms, and the third line shows any notices the UPS has posted. (For more

information about alarms and notices, see Chapter 10, “Responding to System Events.”)

B

The battery charge box shows the percentage of battery capacity available.

C

The menu box shows the currently selected menu and lists the options available on that menu. The

title at the top of the menu box is also shown below on the menu bar (E). Press the

and

buttons to scroll up and down through the options in the menu box.

D

The currently selected option is highlighted in the menu box. Press the

and

buttons to move

the highlight up or down. The data in the information area (G) changes accordingly.

E

The menu bar lists the titles of the menus. The title of the menu currently displayed in the menu

box is highlighted. When you press the

and

buttons to move the highlight left or right, the

data in the menu box and the information area change accordingly.

F

The timestamp shows the current date and time. This date and time are recorded in the Event Log

when a notice or alarm is activated.

G

The information area contains data about UPS status and operations. Select a menu option to

display statistics or graphics.