3 meters printout – [ctrl]+[m – Eaton Electrical Powerware 9315 User Manual

Page 57

Advertising
background image

Communication

7-11

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

7.6.3 Meters Printout – [Ctrl]+[M]

This key sequence prints the current readings of the UPS system meters. The input area

shows the phase-to-phase voltage, frequency, and phase current of the incoming utility,

followed by the kVA, kW, and power factor measurements. The output area shows the

same information for the power being output by the UPS. The Bypass area shows the

phase-to-phase voltage of the bypass source. The Battery area displays the DC voltage (V)

and the DC current (I). Figure 7-7 shows a sample Meters printout.

Input

Output

Bypass

Battery

VAB

480

VBC VCA

KW

379

KVA

399

IA

IB

IC

FREQ

60.0

PF

0.95

V

540

I

0

480

480 480

480

480

VAB

480

VBC

VCA

480

480

IA

IB

IC

361

361

361

IN

0

VAB

480

VBC

VCA

480

480

FREQ

60.0

KVA

300

KW

240

PF

0.80

Uninterruptible Power System

UPS System Normal

Alarm:

None

Notice:

None

03 JAN 1997

14:22:49

+

Figure 7-7. System Meters

Advertising