3 enable/disable default functions – Eaton Electrical Powerware 9315 User Manual

Page 60

Advertising
background image

Communication

7-14

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

7.7.3 Enable/Disable Default Functions

From this menu you may either enable the building alarms for general functions or special

functions such as On Generator, Go To Bypass, and Go To UPS. You may also customize the

alarm messages from this menu. When 1 is selected from this menu, the following menu is

displayed:

Enable/Disable Default Functions

1. Enable/Disable Go To Bypass
2. Enable/Disable Go To UPS
3. Enable/Disable On Generator
4. Enable/Disable Building Alarm
5. Return to Program Building Alarms Menu
Enter Selection:

If you select entry 1-3 from this menu, the following menu appears:

Enable/Disable (Function)

Enabled Building Alarm Number(s)

1 4

Enter E# to Enable Building Alarm Number #

Enter D# to Disable Building Alarm Number #

Enter <CR> for No Change

Enter Selection:

Where (Function) indicates the function the building alarm is being programmed for. The

line following the Enabled Building Alarm Number(s) label indicates which building alarms

are currently enabled for the function. (In this example, Building Alarms 1 and 4 are

enabled.) A building alarm can only be programmed for one special function at a time

from these menus. Enabling a building alarm for a special function automatically enables

the alarm. If you disable a special function, the building alarm is also disabled.

If you select entry 4 from this menu, the following menu appears:

Enable/Disable Building Alarm

Enabled Building Alarm Number(s)

1 4

Enter E# to Enable Building Alarm Number #

Enter D# to Disable Building Alarm Number #

Enter <CR> for No Change

Enter Selection:

The line following the Enabled Building Alarm Number(s) label indicates which building

alarms are currently enabled. (In this example, Building Alarms 1 and 4 are enabled.)