2 entire log – [ctrl]+[p – Eaton Electrical Powerware 9315 User Manual

Page 56

Advertising
background image

Communication

7-10

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

7.6.2 Entire Log – [Ctrl]+[P]

This key sequence prints the entire Event History Log of the UPS at the time the data is

requested. The printout begins with the oldest alarm entry in the queue and ends with the

most recent. Any alarms that occur while the Event History Log is printing are included in

chronological order.

The Event History Log lists up to 400 system events in chronological order with the most

recent event listed last. Figure 7-6 shows a sample Event History Log printout.

Event History Log

Event Description

MAY 12

12

12

12

12

12

12

12

JUN 04

16:41:19.3

16:41:29.1

16:41:42.4

16:42:05.5

16:42:46.8

16:43:15.8

16:43:42.4

16:44:29.1

12:16:35.9

COMMAND: Keyswitch On

STATUS:

Auto Mode

COMMAND: Rectifier Commanded On

STATUS:

Inverter On

STATUS:

Rectifier On

STATUS:

Inverter Contactor (3) Closed

STATUS:

Bypass Contactor (K4) Open

NOTICE:

Room High Temperature

Uninterruptible Power System

UPS System Normal

Alarm:

None

Notice:

None

03 NOV 1997

14:23:45

STATUS:

Inverter Normal

0421

1000

2030

2202

32

4001

Figure 7-6. Event History Log