Communication

7-16

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

7.7.5 Program Unit Name

If Program Unit Name is selected from the main menu, the following is displayed:

Program Unit Name

Unit Name:

Enter New Name or <CR> No Change:

NOTE

Unit Name is 45 characters maximum.

The current unit name is displayed on the second line of the display and in the headers of

prints from Terminal mode. If a change is desired, the new unit name should be entered at

the prompt. The unit name is 45 characters maximum and includes spaces and any

punctuation. If the user wants to center the text portion of the name, the appropriate

number of leading spaces should be included when entered.

7.7.6 Adjust Output Voltage

If Adjust Output Voltage is selected from the main menu, the following menu is

displayed:

Adjust Output Voltage

Output Voltage Setup:

480

Output Voltage Range:

456 - 504

Enter Desired Output Voltage Setup:

The output voltage desired can then be entered or a carriage return for no change. Only

values within the range are accepted.

7.7.7 Change Password

If Change Password is selected from the main menu, the following menu is displayed:

Change Password

Enter New Password:

Verify New Password:

NOTE

Password must be six characters in length.

<CR> to return with no change.

The password changes if the user enters and verifies the password. The entry must be six

characters.