Using the Monitor Panel

5-3

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

You can use the LCD screen and the buttons beneath it to:

Ī

Monitor UPS operation

Ī

Look at a log of UPS events (alarms, notices, and commands)

5.2 Using the Buttons

The buttons below the LCD screen are labeled with arrows indicating their functions:

Ī

Press the

and

buttons to move through the options in a menu, or to scroll through

the list of alarms and notices in the event log.

Ī

Press the

and

buttons to move through the menu titles on the menu bar. Press

them simultaneously to silence the horn, or to test the lamps behind the status

indicators.

Ī

Press the

button to toggle the use of the

and

buttons between the menu box

and the information area.

5.3 Adjusting the Contrast

Use the buttons to adjust the contrast on the LCD screen. Hold down the

button, then

press the

button to increase the contrast or the

button to decrease the contrast.

5.4 Using the Load Off Button

The LOAD OFF button is red and covered by a clear plastic shield. In an emergency, you

can press this button to cut off utility power to the power processing unit of the UPS and

to the critical load. For more information, see Chapter 11, “Using the LOAD OFF Button.”

C A U T I O N

All power to the critical load is lost when you press the LOAD OFF button. You should use the

LOAD OFF button only when you want to de-energize the critical load.