Using the Monitor Panel

5-4

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

5.5 Reading the Status Indicators

The six symbols on the left side of the monitor panel are status indicators. They are backlit

by colored light emitting diodes (LEDs), and they work in conjunction with the alarm horn

to let you know the operating status of the UPS.

Indicator

Symbol

Indicator

Name

Description

Normal

This green symbol is lit when the UPS is operating in Normal mode.

The PPU is supplying power to the critical load.

Battery

This yellow symbol is lit when the UPS is operating in Battery mode.

Because Battery mode is a normal condition of the UPS, the Normal

indicator also remains lit.

Bypass

This yellow symbol is lit when the UPS is operating in Bypass mode.

The critical load is supported by the bypass source. The Normal

indicator is not lit when the system is in Bypass mode.

Notice

This yellow symbol is lit when the system needs attention. The LCD

screen shows all active notices. Some notices may be accompanied by

an audible horn. To silence the horn, press the

and

buttons

simultaneously. The Notice indicator may be lit along with other

indicators.

Alarm

This red symbol is lit when a situation requires immediate attention.

The LCD screen shows the highest priority active alarms. All alarms are

accompanied by an audible horn. To silence the horn, press the

and buttons simultaneously. The Alarm indicator may be lit along

with other indicators.

Standby

This yellow symbol is lit when electricity is present in the PPU of the

UPS and the Normal indicator is not lit. During normal startup, this

indicator illuminates until the the UPS transfers to Normal mode, at

which point the Normal indicator is lit. During normal shutdown, the

Standby indicator is lit until all energy in the UPS is dissipated and

shutdown is complete.

For more information about audible horns, see “System Event Horns” on page 10-1.

To test the LEDs behind the status indicators, press the

and

buttons simultaneously

for three seconds. All the indicators should illuminate while you hold down these buttons.

If any indicator does not illuminate, its LED may need to be replaced. Contact your Eaton

service representative if you have a problem with the indicator LEDs.

5.6 Using the Menu Options

The UPS menus allow you to display data in the information area to help you monitor and

control UPS operation. The following menus and options are available:

Ī

Meters - Displays UPS performance meters for the system or critical load.

Ī

Events - Displays the list of Active System Events and a historical log of system events.

Ī

Statistics - Displays statistical information about UPS operations for the battery, load, or

line.