ADDITIONAL UPS FEATURES

EATON Powerware

®

5130 Rack/Tower UPS (1250–3000 VA) User’s Guide

S 164201730 Rev 2

www.powerware.com

44

Table 6. Voltage Threshold Options (continued)

PW5130G3000-XL2U Function

Factory Setting

Other Available Settings

High threshold for transfer to battery

263 Vac

Low threshold for transfer to battery

160 Vac

Fader activation threshold

229 Vac

Booster activation threshold

177 Vac

Maximum input-voltage range

Disabled

Enabled

2

2

Low threshold for transfer to battery is 150V.

Table 7. UPS Sensitivity Options

Function

Factory Setting

Other Available Settings

UPS-sensitivity level

Normal

High or low

Table 8. UPS On/Off Options

Function

Factory Setting

Other Available Settings

Automatic start

Enabled

Disabled

Cold start

Enabled

Disabled

Forced shutdown

Enabled

Disabled

Energy-savings mode

Disabled

Enabled

UPS ON/OFF controlled by software

Enabled

Disabled

Battery level before restart

0%

0–100%

Table 9. Battery Options

Function

Factory Setting

Other Available Settings

Battery-test intervals

Weekly

No test / daily test / monthly test

Low-battery warning

20%

0–100%

Battery protection against deep discharge

Enabled

Disabled

Audio alarm

Enabled

Disabled

Additional battery module

Automatic detection of number of

battery modules

For specific batteries, 25–81 Ah