Eaton Electrical Powerware 5130 Rack/Tower UPS 1250-3000 VA User Manual

Page 58

Advertising
background image

SPECIFICATIONS

EATON Powerware

®

5130 Rack/Tower UPS (1250–3000 VA) User’s Guide

S 164201730 Rev 2

www.powerware.com

52

Table 11. High-Voltage Model Specifications

Model Number

Power Levels

(Rated at

Nominal Inputs)

AC Input

Output on Battery Power

Nominal

Voltage

Voltage

Range

1

Frequency

Range

2

Voltage

3

Frequency

PW5130i1250-XL2U

1250 VA, 1150W

220–240V

160–294V

47–70 Hz (50 Hz

system),

56.5–70 Hz (60 Hz

system)

230V

(+6/-10%)

50/60 Hz

±0.1%

PW5130i1750-XL2U

1750 VA, 1600W

PW5130i2500-XL2U

2500 VA, 2250W

PW5130i3000-XL2U

3000 VA, 2700W

PW5130i3000-XL3U

PW5130G3000-XL2U

3000 VA, 2700W

208V

160–263V

208V

(+6/-10%)

1

The high and low thresholds can be adjusted using the UPS Configuration tool (see page 43).

2

Up to 40 Hz in low-sensitivity mode (programmable using the UPS Configuration tool).

3

Adjustable to 100V (10% derating of output power) 120/127V.

Table 12. Weights and Dimensions

Low-Voltage Model Number

Dimensions (WxHxD)

Weight

PW5130L1250-XL2U

440

Ч

86

Ч

509 mm

17.3”

Ч

3.4”

Ч

20.0”

24.6 kg (54.3 lb)

PW5130L1750-XL2U

26.3 kg (58.0 lb)

PW5130L2500-XL2U

440

Ч

86

Ч

634 mm

17.3”

Ч

3.4”

Ч

25.0”

34.7 kg (76.4 lb)

PW5130L3000-XL2U

35.3 kg (77.9 lb)

PW5130L3000-XL3U

440

Ч

131

Ч

484 mm

17.3”

Ч

5.2”

Ч

19.0”

33.8 kg (75.5 lb)

High-Voltage Model Number

Dimensions (WxHxD)

Weight

PW5130i1250-XL2U

440

Ч

86

Ч

509 mm

17.3”

Ч

3.4”

Ч

20.0”

24.3 kg (53.6 lb)

PW5130i1750-XL2U

PW5130i2500-XL2U

440

Ч

86

Ч

634 mm

17.3”

Ч

3.4”

Ч

25.0”

33.8 kg (74.5 lb)

PW5130i3000-XL2U

PW5130G3000-XL2U

440

Ч

86

Ч

634 mm

17.3”

Ч

3.4”

Ч

25.0”

35.3 kg (77.9 lb)

PW5130i3000-XL3U

440

Ч

131

Ч

484 mm

17.3”

Ч

5.2”

Ч

19.0”

34.3 kg (75.6 lb)

Advertising