UPS MAINTENANCE

EATON Powerware

®

5130 Rack/Tower UPS (1250–3000 VA) User’s Guide

S 164201730 Rev 2

www.powerware.com

49

How to Replace Extended Battery Modules

To replace the Extended Battery Modules (EBMs):

1.

Unplug the EBM cable from the UPS.

If additional EBMs are installed, unplug the EBM cable from the
battery connector on each EBM.

2.

Unplug the EBM communication cable from the RJ-11 port. Repeat
for each EBM.

3.

For tower models only. Remove the joining bracket between cabinets.

EBM Communication
Cable

EBM Cable

EBM Battery Connectors

Joining Bracket

Figure 29. EBM Connections (230V Tower Model Shown)