TROUBLESHOOTING

EATON Powerware

®

5130 Rack/Tower UPS (1250–3000 VA) User’s Guide

S 164201730 Rev 2

www.powerware.com

58

Table 17. Troubleshooting Guide

Alarm or Condition

Possible Cause

Action

When starting the UPS with the

button, all the indicators turn on

once, the alarm beeps once, and
then

indicator remains on.

The remote power-off (RPO)
contact has been activated to
shut down the UPS and now
prevents restart.

Set the contact back to its normal position
and press the

button to restart.

The

button,

and

indicators are on and all the
bar graph indicators flash.

μ

The percent load is greater than
the set overload level or UPS
capacity.

Check the power drawn by the connected
devices and disconnect any non-priority
devices. Check the overload setting.

The

button and

indicator

are on and all the

bar graph

indicators flash.

A critical overload has occurred.
If utility power fails, the load will
not be protected in Battery
mode.

Check the power drawn by the connected
devices and disconnect any non-priority
devices.

The

indicator is on and all the

bar graph indicators flash.

A battery fault has been
detected during the automatic
test.

Replace the battery (see “Replacing
Batteries” on page 46).

The

indicator alone is on and

the alarm sounds continuously.

UPS fault condition. The load is
not supplied.

Contact your service representative.