Chapter 7 specifications – Eaton Electrical Powerware 5130 Rack/Tower UPS 1250-3000 VA User Manual

Page 57

Advertising
background image

EATON Powerware

®

5130 Rack/Tower UPS (1250–3000 VA) User’s Guide

S 164201730 Rev 2

www.powerware.com

51

Chapter 7

Specifications

Filter

Transformer

“AVR”

Charger

Inverter

Battery

Figure 30. Block Diagram

Table 10. Low-Voltage Model Specifications

Model Number

Power Levels

(Rated at

Nominal Inputs)

AC Input

Output on Battery Power

Nominal

Voltage

Voltage

Range

1

Frequency

Range

2

Voltage

3

Frequency

PW5130L1250-XL2U

1250 VA, 1150W

120V

89–151V

47–70 Hz (50 Hz

system),

56.5–70 Hz (60 Hz

system)

120V

(+6/-10%)

50/60 Hz

±0.1%

PW5130L1750-XL2U

1750 VA, 1600W

PW5130L2500-XL2U

2500 VA, 2250W

PW5130L3000-XL2U

2880 VA, 2700W

PW5130L3000-XL3U

1

The high and low thresholds can be adjusted using the UPS Configuration tool (see page 43).

2

Up to 40 Hz in low-sensitivity mode (programmable using the UPS Configuration tool).

3

Adjustable to 100V (10% derating of output power) 120/127V.