ControlWave ExpressPAC Instruction Manual (CI-ControlWave EPAC)

2-12 Installation

Revised

Mar-2011

SW2 Setting

Function

Mode

ON (Disables core updump; factory default)
OFF Core updump

5

SRAM Control

Manages SRAM contents following a low power situation
or a power outage. Values are:
ON (Retain values in SRAM during restarts; factory
default
)
OFF (Reinitialize SRAM) – Data in SRAM lost during
power outage or re-start.

6

System
Firmware

Allows a remote download of system firmware (on units
equipped with boot PROM version 4.7 or higher and
system PROM version 4.7 and higher). Values are:
ON (Enable remote download of system firmware; factory
default
)
OFF (Disable remote download of system firmware)

7

N/A

Not currently used.

8

Enable
WINDIAG

Suspends normal operation and allows diagnostic
routines. Values are:
ON (Permits normal system operation, including the boot
project, and disables the WINDIAG diagnostics from
running; factory default)
OFF (Allow WINDIAG to run test; disable boot project and
normal system operation.)

Note: Setting both switch 8 and switch 3 to OFF (closed)

sets all communication ports to 9600 bps operation.
All serial communication ports must be set at 9600
bps before WINDIAG can perform communication
tests.

Note:

Table 2-3 describes switch settings for RS-485 port operation.
You may want to review Section 2.3.7 on RS-485 configuration
before you set these switches.

Table 2-3. RS-485 Configuration Switch SW3

Switch

Setting

Function Mode

1

TX+ to RX+ Loopback / 2-
wire

ON (2-wire operation or loopback enabled)

OFF (4-wire operation and loopback
disabled)

2

TX- to RX- Loopback / 2-
wire

ON (2-wire operation or loopback enabled)

OFF (4-wire operation and loopback
disabled)

3

100 Ohm RX+ Termination

ON (End nodes only)

4

100 Ohm RX- Termination

ON (End nodes only)

5

N/A

Not currently used

6

N/A

Not currently used

Advertising