Emerson Process Management Bristol ControlWave ExpressPAC User Manual

Page 71

Advertising
background image

ControlWave ExpressPAC Instruction Manual (CI-ControlWave EPAC)

Revised Mar-2011

Service & Troubleshooting

5-3

 The screens shown here may appear different depending upon the

version of HyperTerminal you use.

 HyperTerminal requires *.BIN files; newer ControlWave firmware

upgrade files use *.CAB files. In cases such as those, you should use
the Remote System Firmware Downloader.

1.

Connect a null modem cable between COM1 of the
ControlWave ExpressPAC and any RS-232 port on the
associated PC.

2.

Click Start > Programs > Accessories > Communications >
HyperTerminal

3.

If using HyperTerminal for the first time, set the communication
properties (for the PC port) via the Properties Menu as follows:
Bits per second: = 115200, Data bits: = 8, Parity: = None, Stop
bits: = 1, and Flow control: = None and then click OK.

4.

Set CPU/System Controller board switch SW1-3 ON (ON =
Force Recovery).

5.

Apply power; to the ControlWave ExpressPAC. The resident
BIOS initializes and tests the hardware, this process is referred
to as POST (Power On Self Test). Unless there is a problem, the
LCD display shows “RECOV.” See Table 5-1 for information on
other LCD status messages.

6.

From the HyperTerminal Mode menu (Figure 5-1), press the F
key to enter FLASH download. A message warns that the
FLASH is about to be erased; press the Y key at the prompt. The
screen displays dots as the system erases the flash memory; this
could take a few minutes.

Figure 5-1. HyperTerminal Mode Menu

Advertising