ControlWave ExpressPAC Instruction Manual (CI-ControlWave EPAC)

2-22 Installation

Revised

Mar-2011

Note:

A factory-installed wiring harness connects J4 (COM1) to the
circular 5-pin Local Port connector at the bottom of the enclosure
cover.

Table 2-7. RS-232 COM1 (J4) and COM2 (TB3) Port Connector Pin Assignment

Pin

RS-232

Signal


RS-232 Description

Local Port (RS-232 Pin#)

1

DCD

Data Carrier Detect Input

1 (green wire)

2

RXD

Receive Data Input

2 (red wire)

3

TXD

Transmit Data Output

7 (white wire)

4

DTR

Data Terminal Ready Output

4 (brown wire – Pin 4 connected to pin 4 at TB5
of CPU = external power for local port
communication cable)

5

GND

Power Ground

6 (black wire)

6

DSR

Data Set Ready Input

7

RTS

Request to Send Output

RTS connected to CTS at J4 of CPU for local
port communication cable

8

CTS

Clear to Send Input

RTS connected to CTS at J4 of CPU for local
port communication cable

9

N/A

Table 2-8. RS-232 COM1 (J11) Alternate Connector Pin Assignment

Pin

RS-232

Signal

RS-232 Description

1 GND

Power

ground

2

RXD

Receive data input

3

TXD

Transmit data output

Use the “null modem” cable for full-duplex (PPP protocol)
communications when connecting a ControlWave ExpressPAC to a PC.
(See top part of Figure 2-11.)

Advertising