4 available diagnostics, Available diagnostics -12, Available diagnostics – Emerson Process Management Bristol ControlWave ExpressPAC User Manual

Page 80

Advertising
background image

ControlWave ExpressPAC Instruction Manual (CI-ControlWave EPAC)

1.

Start OpenBSI communications using NetView, TechView, or
LocalView, and select the RTU you want to test.

2.

Select Start >Programs > OpenBSI Tools >Common Tools >
Diagnostics. The Main Diagnostics menu (Figure 5-6) opens.

Figure 5-6. WINDIAG Main Diagnostics Menu

3.

Select the component to be tested. See Section 5.3.4 for a
description of the tests. Enter any prompted parameters (slot #,
etc.). WINDIAG performs the diagnostics and displays pass/fail
results.

After performing all diagnostic testing, exit WINDIAG.

4.

Set switches SW2-3 and SW2-8 on the CPU module to ON. The
ControlWave ExpressPAC should resume normal operation.

5.3.4 Available Diagnostics

WINDIAG’s Main Diagnostics Menu (see Figure 5-6) provides the
following diagnostic selections:

Option

Tests

CPU & Peripherals

Checks the CPU/System Controller board except
for memory.

Analog Output

Checks the AO on the Process I/O board.

High Speed Counter

Checks HSCs on the Process I/O board and

5-12

Service & Troubleshooting

Revised Mar-2011

Advertising