ControlWave ExpressPAC Instruction Manual (CI-ControlWave EPAC)

Revised Mar-2011

Installation

2-13

Switch

Setting

Function Mode

7

RX+ Bias (End Node)

ON (4-wire = Both End nodes only; 2-wire=
One end node only)

OFF = No bias

8

RX- Bias (End Node)

ON (4-wire = Both End nodes only; 2-wire=
One end node only)

OFF = No bias

2.3.2 Setting Jumpers on the CPU/System Controller Board

The CPU has several jumpers.

W1: COM1 CTS usage:

o

1-to-2 Installed = COM1 CTS source is from device.

o

2-to-3 Installed = COM1 RTS to CTS loopback

W2: COM2 CTS usage:

o

1-to-2 Installed = COM2 CTS source is from device.

o

2-to-3 Installed = COM2 RTS to CTS loopback

Note:

You must enable the backup battery by setting jumper W3 to
position 1-2.

W3: Enable/disable battery backup selection:

o

1-to-2 Installed = Enable battery backup.

o

2-to-3 Installed = Disable battery backup

W5: Power supply shut down selection:

o

1-to-2 Installed = 12/24V power supply shut down hysteresis

o

2-to-3 Installed = 6V power supply shut down hysteresis

W6: Power supply shut down selection:

o

1-to-2 Installed = 12V power supply shut down

o

2-to-3 Installed = 6/24V power supply shut down

W7: Power fail trip point hysteresis selection:

o

1-to-2 Installed = 12/24V power fail trip point hysteresis

o

2-to-3 Installed = 6V power fail trip point hysteresis

W8: Power fail trip point selection:

o

1-to-2 Installed = 12V power fail trip point

o

2-to-3 Installed = 6/24V power fail trip point

W12: COM3 configuration selection:

o

1-to-2 Installed = COM3 is RS-232

o

2-to-3 Installed = COM3 is RS-485

W13: COM3 configuration selection:

o

1-to-2 Installed = COM3 is RS-232

o

2-to-3 Installed = COM3 is RS-485