Fig.1c, Fig.2a fig.2b, Installation – Sealey SSC12710 User Manual

Page 4

Advertising
background image

3.2. UNPACKING THE COMPRESSOR.

3.2.1. to avoid damages and to protect the compressor during

transport it is placed on a wooden pallet, to which it is

secured by nuts and bolts. A cardboard cover is then strapped

to the pallet. All the shipping and handling information and

symbols are printed on the compressor packing. using a forklift

truck take the compressor as near as possible to the place

where it is to be installed.

Note! the machine must be

unpacked by qualified personnel using appropriate tools and

equipment.

3.2.2. release the strapping holding the cardboard cover onto the

pallet and with the help of a second person lift the cover up

and off the compressor as shown in fig.1B.

3.2.3. Inspect the compressor for any shortages or damage. If

anything is found to be missing or damaged contact your

supplier.

3.2.4. remove the four sets of nuts and bolts that secure the

compressor feet to the pallet as indicated in fig.1c.

3.2.5. Dispose of the packaging in accordance with local authority

regulations.

3.3. STORING THE PACKEd ANd UNPACKEd COMPRESSOR.

3.3.1. If the compressor is not to be unpacked immediately store it in

a dry place at a temperature between +5°c and +40°c and

sheltered away from the weather. If the compressor is not used

immediately after unpacking it, place sheets over it to protect it

from dust, which may settle on the components. the oil is to be

replaced and the operational efficiency of the compressor is to

be checked if it is not used for long periods.

fig.1C

4.1. The compressor must be installed as indicated in these

instructions. Any machine failure due to incorrect

installation will invalidate the warranty.

4.1.1 the compressor should be operated on a flat surface.

4.1.2. check the oil level, consulting the oil level inspection window.

use only synthetic oil (see maintenance section for oil

specification).

4.1.3. confirm the mains voltage corresponds with the voltage shown

on compressor data plate. Have a qualified electrician wire in

the compressor in accordance with section 1.1.

4.1.4. When fully installed, start the compressor and ensure that

everything is in good working order before operational use.

check the direction of rotation (see section 4.8.1) to

confirm correct wiring of 3-phase plug. re-check oil levels.

4.2. ROOM TEMPERATURE.

4.2.1. for correct functioning of the compressor the room

temperature must not be lower than 5°c or higher than 45°c.

4.2.2. If the compressor is operated at a room temperature

lower than the minimum value, the condensate could be

separated within the circuit resulting in water mixing with the

oil. the resulting deterioration in oil quality would fail to

guarantee the even formation of an effective lubricating film

between moving parts with the possibility of seizure.

4.2.3. If the compressor works at a room temperature higher than

maximum value, the compressor would take in air that is too

hot, which would prevent the heat exchanger from adequately

cooling the oil in the circuit, raising the working temperature of

the machine, thus causing the thermal safety device to trip,

which stops the compressor due to the excessive temperature

of the air/oil mixture at the screw outlet.

4.2.4.

The maximum temperature of the room is to be measured

while the compressor is running.

4.3. vENTILATION REQUIREMENTS.

4.3.1. the room must be provided with outlets that lead outdoors

near the floor and ceiling that will allow the natural circulation

of air. If this is not possible, install some fans or extractors (see

fig.2B) that guarantee an air flow rate 50% higher than that

taken in by the compressor (min. flow 2500m³/h). Ducts for the

inlet and outlet of the air can be used in unfavourable

environments. these ducts must be the same size as the

intake and delivery grills. If these ducts are longer than 3meters

contact the Authorised service centre.

4.4. SPACE REQUIREd FOR MAINTENANCE.

4.4.1. the compressor must be installed in a large room that is well-

ventilated, dust-free and sheltered away from rain and frost.

the compressor takes in a large amount of air that is required

for internal ventilation. A dusty atmosphere would in time

cause damage and inefficient performance. Dust drawn into

the machine will be taken into the air filter causing it to clog

rapidly. Incoming dust will also settle onto the components and

will be blown against the cooling radiator, consequently

compromising the efficiency of the heat exchanger. It is

therefore obvious that the cleanliness of the area in which the

compressor is installed is crucial for the correct efficiency of

the machine, avoiding excessive running and maintenance

costs. to facilitate maintenance and to create a favourable

circulation of air, the compressor must have sufficient free

space all around it as shown in figures 2A & 2B.

4.5. LIGHTING.

4.5.1. the compressor has been designed with the intention of

minimising areas of shade in order to facilitate the operator’s

interaction with the compressor both from a control and a

maintenance point of view. the lighting system in the area of

installation should be configured to further enhance this

interaction and should be considered as crucial for the operator’s

safety. therefore, the room in which the compressor is

installed must be neither under lit nor over lit, and without shadow

zones, dazzling lights or stroboscopic effects due to the lighting.

4. INSTALLATION

fig.2A

fig.2b

Original Language Version

ssc12710 & ssc12710D Issue: 3 - 23/02/12

Advertising
This manual is related to the following products: