Installation instructions – MCZ Forma Wood 75 Dx User Manual

Page 8

Advertising
background image

6

2-INSTALLATION INSTRUCTIONS

CONNECTION TO THE CHIMNEY

The connection to the closed fireplace is very important and must be implemented carefully. The products have an upper or rear smoke

exhaust. The smoke exhaust pipe must be assembled in such a way so as to guarantee its tightness during product operation in negative

pressure and prevent condensation from being formed and conveyed towards the product.

Any manual draught control devices inserted in the pipe should not hermetically seal the internal section of the duct. These dampers

must be equipped with a suitable mechanism to prevent the valve from rotating completely in the closed position. The minimum safety

opening surface must be 3% of the through section and not less than 20 cm². If the smoke duct has a horizontal section, the same should

rise with a minimum slope gradient of 3-5% (3-5 cm per every metre).

The horizontal section of the smoke duct must not be longer than 2 m.

It is forbidden to use flexible and fibre cement pipes. The smoke duct must not cross rooms in which it is forbidden to

install combustion appliances. It is forbidden to use counter-sloping pipes.

EXAMPLE OF CONNECTION TO THE CHIMNEY