MEDC DB3B User Manual

Page 10

Advertising
background image

07/14

© MEDC 2014


The unit is fitted with a volume control which is positioned on the top face of the electronics assembly PCB.
Maximum volume is obtained when this control is turned fully clockwise. When turned fully anti-clockwise the unit
will emit no sound.

Warning: Do not attempt to turn the volume control past its limits of movement as this may cause damage to the
unit.

Stages
For all versions, a 5-way DIP switch selects the stage required for each stage. The settings for the standard stages
are shown in the table below:

Tone table 1:

TONE

No.

TONE FREQ/DESCRIPTION

SWITCH

SETTING

12345

TONE DESCRIPTION

Nominal SPL

(dB(A) @ 1m)

1

Alt Stages 800/970 Hz at 1/4 sec

11111

112

2

Sweeping 800/970 Hz at 7 Hz

11110

Fast Sweep (LF)

111

3

Sweeping 800/970 Hz at 1 Hz

11101

Medium Sweep (LF)

113

4

Continuous at 2850 Hz

11100

111

5

Sweeping 2400-2850 Hz at 7 Hz

11011

Fast Sweep

112

6

Sweeping 2400-2850 Hz at 1 Hz

11010

113

7

Slow Whoop

11001

Slow Whoop

113

8

Sweep 1200-500 Hz at 1 Hz

11000

Din Stage

117

9

Alt Stages 2400/2850 Hz at 2 Hz

10111

111

10

Int Stage of 970 Hz at 1 Hz

10110

Back-up Alarm (LF)

112

11

Alt Stages 800/970 Hz at 7/8 Hz

10101

112

12

Int Stage at 2850 Hz at 1Hz

10100

Back-up Alarm (HF)

112

13

970 Hz at 1/4 sec on 1 sec off

10011

112

14

Continuous at 970 Hz

10010

112

15

554 Hz for 0.1S/440 Hz for 0.4S

10001

French Fire Sound

113

16

Int 660 Hz 150 mS on 150 mS off

10000

Swedish Fire Alarm

108

17

Int 660 Hz 1.8 sec on 1.8 sec off

01111

Swedish Fire Alarm

108

18

Int 660 Hz 6.5 sec on 13 sec off

01110

Swedish Fire Alarm

109

19

Continuous 660 Hz

01101

Swedish Fire Alarm

108

20

Alt 554/440 Hz at 1 Hz

01100

Swedish Fire Alarm

113

21

Int 660 Hz at 7/8 Hz

01011

Swedish Fire Alarm

108

22

Int 2850 Hz 150 mS on 100 mS off

01010

Pelican Crossing

111

23

Sweep 800-970 Hz at 50 Hz

01001

Low Freq. Buzz

109

24

Sweep 2400 -2850 Hz at 50 Hz

01000

High Freq. Buzz

111

25

3x970 Hz pulses 0.5 off, 1.5 off

00111

112

26

3x2850 Hz pulses 0.5on/0.5off, 1.5 off

00110

112

27

Int 3100 Hz 0.32s on/0.68s off

00101

105

28

Continuous 1400 Hz

00100

125

29

Spare / Custom tone

00011

30

Spare / Custom tone

00010

31

Spare / Custom tone

00001

32

Spare / Custom tone

00000


Note: If special tones were requested at the time of ordering, please see the separate tones list supplied with the unit
for details of these special tones and their respective switch settings.

4.0 OPERATION

The sounder is available in various AC input voltage versions and a single DC input voltage version.

For AC versions, the nominal operating voltage is stated on the unit label and the supply voltage tolerance is ±10%.
For DC versions, the absolute input voltage range is 11.0Vdc to 57.6Vdc.

If using an EOL resistor with a value between 700Ω and 2KΩ the maximum voltage should be limited to 28.8Vdc, if
using an EOL resistor with a value between 470Ω and 700Ω the maximum voltage should be limited to 26Vdc.

Advertising
This manual is related to the following products: