Isolated 4-20 ma transmitter output – Precision Digital PD6300 User Manual

Page 13

Advertising
background image

Model PD6300 Pulse Input Rate/Totalizer

Instruction Manual

13

RELAY RESET

User selectable via front panel buttons, digital inputs, or PC

1.

Automatic reset only (non-latching), when the in-
put passes the reset point or total is reset to zero.

2.

Automatic + manual reset at any time (non-latching)

3.

Manual reset only, at any time (latching)

4.

Manual reset only after alarm condition has cleared
(L)

Note: Front panel button or digital input may be assigned to

acknowledge relays programmed for manual reset.

TIME DELAY

0 to 999.9 seconds, on & off relay time delays
Programmable and independent for each relay.

FAIL-SAFE
OPERATION

Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.

In case of power failure, relay will go to alarm state.

AUTO
INITIALIZATION

When power is applied to the meter, relays will reflect the
state of the input to the meter.

Isolated 4-20 mA Transmitter Output

OUTPUT
SOURCE

Rate/process, total, grand total, max, min, set points 1-8,
Modbus input or manual control mode

SCALING RANGE 1.000 to 23.000 mA for any display range.

CALIBRATION

Factory calibrated: 0.0 to 1000.0 = 4-20 mA output

ANALOG OUT
PROGRAMMING

23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break

ACCURACY

± 0.1% FS ± 0.004 mA

TEMPERATURE
DRIFT

0.4 µA/

C max from 0 to 65C ambient,

0.8 µA/

C max from -40 to 0C ambient

Note: Analog output drift is separate from input drift.

ISOLATED
TRANSMITTER
POWER SUPPLY

Terminals I+ & R: 24 VDC

 10% @ 40 mA maximum; may

be used to power the 4-20 mA output or other devices.
Refer to Figure 6 on page 21 and Figure 14 on page 26.

EXTERNAL LOOP
POWER SUPPLY

35 VDC maximum

OUTPUT LOOP
RESISTANCE

Power supply

Minimum

Maximum

24 VDC

10

 700

35 VDC (external)

100

 1200