Specifications, General – Precision Digital PD6300 User Manual

Page 9

Advertising
background image

Model PD6300 Pulse Input Rate/Totalizer

Instruction Manual

9

SPECIFICATIONS

Except where noted all specifications apply to operation at +25°C.

General

DISPLAY

Main display: 0.6" (15 mm) high, red LEDs
Second display: 0.46" (12 mm) high, red LEDs
6 digits: each (-99999 to 999999), with lead zero blanking.

DISPLAY
INTENSITY

Eight user selectable intensity levels

DISPLAY
UPDATE RATE

Rate: 10 per second; up to 1 per 100 seconds (and is a
function of Low Gate setting)
Total: 10 per second (fixed)

OVERRANGE

Display flashes

999999

DISPLAY
ASSIGNMENT

The main (Big) and small (Little) displays may be assigned
to rate, total, grand total, alternate rate & total, max/min,
units (small display only), set points, and Modbus input.

PROGRAMMING
METHODS

Four front panel buttons, digital inputs, PC and MeterView Pro
software, Modbus registers, or cloning using Copy function.

RECALIBRATION All ranges are calibrated at the factory to read frequency in

Hz. No recalibration required.

MAX/MIN
DISPLAY

Max/min readings reached by the process are stored until
reset by the user or until power to the meter is turned off.

PASSWORD

Three programmable passwords restrict modification of
programmed settings and two prevent resetting the totals.

Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs.
Total: Prevents resetting the total manually
Gtotal: Prevents resetting the grand total manually

NON-VOLATILE
MEMORY

All programmed settings are stored in non-volatile memory
for a minimum of ten years if power is lost.

POWER
OPTIONS

85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max
or jumper selectable 12/24 VDC

 10%, 15 W max

FUSE

Required external fuse: UL Recognized, 5 A max, slow
blow; up to 6 meters may share one 5 A fuse

ISOLATED
TRANSMITTER
POWER SUPPLY

Terminals P+ & P-: 24 VDC

 10% @ 200 mA max (standard),

(12/24 VDC powered models rated @ 100 mA max).
5 or 10 VDC @ 50 mA max, selectable with internal jumper J4.

ISOLATION

4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply

Advertising