Model PD6300 Pulse Input Rate/Totalizer

Instruction Manual

49

Calibrating the Meter with External Source (Cal)

To scale the meter without a signal

source refer to K-Factor Calibration
(Factor) on page 43 or Scaling the

Meter (SCALE) on page 45

The meter can be calibrated to display the process variable in engineer-
ing units by applying the appropriate input signal and following the cali-
bration procedure.
The use of a calibrated signal source is strongly recommended to cali-
brate the meter.

CAL

Prog

Inp 1

CAL

Inp 1

I n p 1

Inp 2

CAL

Inp 2

I n p 2

dis 1

Inp 1

00

0

00.0

d i s 1

dis 2

Inp 2

1

0000.0

d i s 2

The display

flashes while

sensing the

inputs

There is no need to warm up the meter before

performing the calibration procedure.