Model PD6300 Pulse Input Rate/Totalizer

Instruction Manual

61

Relay Operation Details

Overview

The relay capabilities of the meter expand its usefulness beyond simple
indication to provide users with alarm and control functions. These capa-
bilities include front panel alarm status LEDs as well as either 2 or 4 op-
tional internal relays and/or 4 external relays expansion module. Typical
applications include high or low flow alarms and basic batch control.
There are four basic ways the relays can be used:
1. High or Low Alarms with Latching or Non-Latching Relays
2.

Simple On/Off Control with 100% Adjustable Deadband

3. Sampling (Based on Time)
4. Alternation Control for up to 8 Relays

Relays Auto Initialization

When power is applied to the meter, the front panel LEDs and alarm
relays will reflect the state of the input to the meter. The following table
indicates how the alarm LEDs and relays will react on power-up based
on the set and reset points:

Alarm #

HI or LO

Alarm

Set

Point

Reset

Point

Power-Up

Reading

Relay &

LED

1 HI

1000

500 499 Off

2 LO

700

900 499 On

3 LO

250

400 499 Off

4 HI

450

200 499 On

Fail-Safe Operation

The following table indicates how the relays behave based on the fail-
safe selection for each relay:

Fail-Safe

Selection

Non-Alarm State

Alarm State

Power Failure

NO NC NO NC

Off Open

Closed

Closed

Open

Relays go to
non-alarm state

On Closed

Open

Open

Closed

Relays go to
alarm state

Note: NO = Normally Open, NC = Normally Closed. This refers to the
condition of the relay contacts when the power to the meter is off.