+10ºC

+1ºC

-2ºC

The original temperature is sho wn within the range of 0ºC (Range Low) and 100ºC (Range High).
Bias points have been used to adjust the displayed temperature as shown in the graph in Fig 1.

To establish this bias, the settings are shown below.

Temperature Bias Value (BS0 through BS4) = Temperature After Bias - Actual Temperature

Display temperature after bias at 600ºC actual temperature = P

Fig 2: Bias Formula Calculation

Original

Temperature

Temperature After Bias

0ºC = BS0

10ºC = BS1

10ºC = BS2

50ºC = BS3

0ºC = BS4

BSP1

BSP2

BSP3

RL

RH

Original
Temp

Fig 1: Temperature Bias

0ºC = BS0

RL

BSP3

RH

BSP1

BSP2

Original Temperature

Temperature

After Bias

BS4

75ºC

0ºC

25ºC

50ºC

100ºC

-3ºC = BS3

-2ºC = BS1

+1ºC = BS2

0ºC = BS4

-3ºC

Example 1:

Temperature Settings to Establish Where the Bias Occurs

RL

BSP1

BSP2

BSP3

RH

0ºC

25ºC

50ºC

75ºC

100ºC

Bias Offset for Each Point

BS0

BS1

BS2

BS3

BS4

0ºC

-2ºC

+1ºC

-3ºC

0ºC

P = 600 + (600 - BPS2) x

BSP3 - BSP2

BS3 - BS2

+ BS2

Example 2:

600ºC -

100ºC

0ºC

500ºC

800ºC

1000ºC

+10ºC

+PºC

+50ºC

P = 600 + (600 - 500) x

800 - 500

50 - 10

+ 10 = 623ºC Temperature After Bias