5.8 Retransmission Group (G.RET)

This parameter sets the type of retransmission operation to use. Options are PV, SP, MV,
and LPS. See notes below for an explanation of the retransmission types.
The default setting is PV.

PV

These parameters are used to scale the retransmitting output. They set the high and low
limits for th e retransmission output scale, as shown below. The retransmitting outputs will
transmit 4 mA at th e low limit (RETL) and 20 mA at the high limit (RETH) values. These
limi ts are used when the retransmission type is set to PV or SP.

RETL

4.0 mA

12.0 mA

RETH

20.0 mA

PV

PV

PV and SP Type Retransmission Scale
PV type retransmits based on the input value, SP retransmits based on the set point value.

0.0%

(No Output)

4.0 mA

12.0 mA

100.0%

(Maximum Output)

20.0 mA

MV Type Retransmission Scale
MV type retransmits based on the full scale output and what is currently being transmitted by the control outputs

Display

Parameter

Setting Range

Unit

Default

Remark

RET

RETH

RETL

Select Ret Type

PV, SP, MV, LPS

ABS

PV

Ret Scale

High Limit

T/C, RTD: INRH to INRL

mV, V: INSH to INSL

RETH > RETL

AEU

INRH

Only valid

when RET

is set to

PV or SP

Ret Scale

Low Limit

AEU

INRL

PV

Press SET/ENT key to select retransmission group. (Refer to parameter map.)

g.ret

ret

retH
retl

G.AT G.SP G.PID PWD G.CTL G.IN

G.COM G.RET G.ALM G.OUT

Retransmission Group Parameter Summary

LPS Type Retransmission
LPS (Loop Power Suppy) retransmitting outputs will transmit a 14-18 VDC @ 20 mA power supply output.