NOTE

Display

Parameter

Setting Range

Unit

Default

Remark

IN.SL

IN.FL

BSL

RSL

BSP1

BSP2

BSP3

BS0

BS1

BS2

BS3

BS4

Min Input

Value Scale

0.0

mV, V

PV Filter

OFF, 1 to 120

sec

OFF

Open Sensor

Behavior

OFF, UP, DOWN

ABS

UP

Not Used for

VDC Input

RJC Operation

ON, OFF

ABS

ON

Only Used for

TC Input

Reference Bias

Point 1

AEU (0.0 to 100.0%),

RL

≤BSP1≤BSP2≤BSP3≤RH

AEU

AEU

(100.0%)

Reference Bias

Point 2

AEU (0.0 to 100.0%),

RL

≤BSP1≤BSP2≤BSP3≤RH

AEU

AEU

(100.0%)

Reference Bias

Point 3

AEU (0.0 to 100.0%),

RL

≤BSP1≤BSP2≤BSP3≤RH

AEU

AEU

(100.0%)

Bias Value for RL

Point

GEU (-100.0 to 100.0%)

GEU

0

Bias Value at

BSP1

GEU (-100.0 to 100.0%)

GEU

0

Bias Value at

BSP2

GEU (-100.0 to 100.0%)

GEU

0

Bias Value at

BSP3

GEU (-100.0 to 100.0%)

GEU

0

Bias Value

at RH

GEU (-100.0 to 100.0%)

GEU

0

IN-T

IN-U

IN.RH

IN.RL

IN.DP

IN.SH

Input Type

Refer to Table 1: Universal Input Selection

ABS

TC.K1

Display Unit

ºC / ºF

ABS

ºC

T/C, RTD

Max PV

Display Range

Within sensor input range

Refer to Table 1

INRH > INRL

AEU

1370

Min PV

Display Range

AEU

-200

Decimal Point

Position

0, 1, 2, or 3

ABS

1

mV, V

Max Input

Value Scale

-1999 to 9999
INSH > INSL

Decimal position determined by IN.DP

ABS

100.0

mV, V

There are two types of engineering units values used in the setting of parameters, absolute
engineering units (AEU) and general eng ineering units (GEU). An AEU parameter is set using an
absolute value engineering unit that represents a specific point, such as a specific temperature or
voltage level. An GEU parameter is set using engineering units, however it is a general value, and not
tied to any input or output level.

For example: When establishing input bias, parameter BSP1 sets the specific PV value where bias
point one will occur. This parameter has a unit designation of AEU. BS1, the amount of offset at BSP1
is set in engin eering units, however this parameter occurs at whatever BSP1 is set to, and therefore
does not have an absolute setting related to any input or output, it is just the amount of offset at where
BSP1 occurs. While one is related to an absolute input value, and the other stand alone value, both are
set as engineering units, such as BSP1 set as 100ºC and BS1 set as 3ºC.

Input Group Parameter Summary

PD540 Series Nova Digital Process and Temperature Controller

Instruction Manual