Precision Digital PD540 User Manual

Page 30

Advertising
background image

OH

(90%)

100

50

0

50

100

DB

(20%)

0

0

50

100

OL-LIMIT

(0 %)

OH-LIMIT

(105%)

OUTPUT

COOL

HEAT

HYS

Fig 8: Heating PID and Cooling On/Off Outputs

Display

Parameter

Setting Range

Unit

Default

Remarks

n.MR

n.Manual Reset

-5.0 to 105.0%

%

50.0%

Used if I=0,

or H/C Model

ARW

FUZY

PID

n.P

n.I

n.D

Anti-Reset Wind-Up

Auto or 50.0 to 200.0%

%

Auto

Fuzzy

OFF, ON

ABS

OFF

PID Number

MENU (0), 1, 2, 3, or 4

ABS

MENU

n.Proportional Band

0.1 (H/C Models:0.0) to 999.9%

%

10.0%

n.Integral Time

OFF, 1 to 6000 seconds

sec

120 sec

n.Derivative Time

OFF, 1 to 6000 seconds

sec

30 sec

n.DB

n.Deadband

-100.0 to 50.0%

%

3.0%

H/C

Models Only

n.Pc

n.Ic

n.Dc

n.Proportional Band

for Cooling Side

0.0 (ON/OFF Control) or 0.1 to 999.9%

%

10.0%

H/C

Models Only

n.Integral Time for

Cooling Side

OFF, 1 to 6000 sec

sec

120 sec

H/C

Models Only

n.Derivative Time for

Cooling Side

OFF, 1 to 6000 sec

sec

30 sec

H/C

Models Only

1.RP

Reference Point 1

AEU (0.0%), 1.RP < 2.RP

AEU

100.0%

PID Zone 1

2.RP

Reference Poin t2

1.RP < 2.RP < AEU (100.0%)

AEU

100.0%

PID Zone 2

RHY

Reference

Hysteresis

GEU (0.0 to 10.0%)

GEU

0.3%

PID Zone 3

RDV

Reference

Deviation

GEU (0.0 to 100.0%)

GEU

0.0%

PID Zone 4

PID Group Parameter Summary

C.MOD

Control Mode

Differential of Deviation Value (d. dV) or

Process Variable (d. PV)

ABS

d. dV

PD540 Series Nova Digital Process and Temperature Controller

Instruction Manual

30