5.6 Auto-Tuning Group (G.AT)

The parameter to activate the auto-tuning function.
When AT is set to ON, auto-tu ning will begin (indicated by the MAN light blinking). This
parameter cannot be used if the controller is in STOP mode.

PV

PV

The auto-tuning feature is used to let the controller measure process characteristics and automatically set the most

appropriate values for the PID parameters. During the initial auto-tuning process, the control outputs will function
in an On/Off condition, and the controller will use the responses to calculate the needed PID values. During this
setup process, the MAN LED on the controller will blink.

Start the auto-tuning process a fter setting a desired set point. Auto-tuning will set the PID parameters for the PID

zone which the set point is in, based on the PID reference point (RP) entered.

Auto-Tuning (AT)

PID Control

ON

OFF

ON

OFF

ON

Control Output

SP

RP

RL

RH

Auto-Tuning On

(On/Off Operation, MAN LED Blinking)

2.PID

1.PID

Fig 9: Auto-Tuning

AT group selection does not appear if operating in On/Off mode or when set for manual output control.

Press SET/ENT key to select AT group. (Refer to parameter map in section 3.)

?

NOTE

?

NOTE

G.AT G.SP G.PID PWD G.CTL G.IN

G.COM G.RET G.ALM G.OUT

PD540 Series Nova Digital Process and Temperature Controller

Instruction Manual