Po poc – Precision Digital PD540 User Manual

Page 21

Advertising
background image

SP

SP

OUT1 Relay

Condition

PV

PV

HYS.L

Display

Parameter

Setting Range

Unit

Default

Remark

SUB2

O.ACT

CT

OH

OL

PO

Select Output

HEAT, COOL, ALM1, ALM2, ALM3, RUN

ABS

ALM3

Option

Reverse and

Forward

REV, FWD

ABS

REV

Cycle Time 1

1 to 300 sec

sec

2 sec

High Limit value

of Output

OL + 1 digit to 105.0%

HC models: 0 to 105.0%, however OH>OL

%

Low Limit value

of Output

-5.0% to OH setting

HC Type: 0 to 105.0%, However OH>OL

%

Preset Output

-5.0 to 105.0%

H/C Type : 0.0 to 105.0%

%

OUT1

OUT2

OUT3

HEAT

SUB1

Select Output

HEAT, COOL, ALM1, ALM2, ALM3, RUN

ABS

ALM1

Select Output

HEAT, COOL, RET

ABS

HEAT

Select Output

HEAT, COOL, RET

ABS

RET

Models with

OUT3 Only

Select Output

Type

SSR, SCR

ABS

SSR

When OUT 2,

3, Set for HEAT

Select Output

HEAT, COOL, ALM1, ALM2, ALM3, RUN

ABS

ALM2

Option

COOL

Select Output

Type

SSR, SCR

ABS

SSR

When OUT 2,

3, Set for COOL

CTc

Cycle Time 2

1 to 300 sec

sec

H/C Models Only

POc

Preset Output

0.0 to 105.0%

%

H/C Models Only

This parameter establishes the percent output transmitted by the control outputs when the
controller is in STOP m ode, or when an error condition occurs such as a PID algorithm
error, A/D error, or open sensor error is detected.

PV

This parameter establishes the percent output transmitted by the COOL control outputs in
a Heating & Cooling controller model when the controller is in STOP mode, or when an
error condition occurs.

PV

0.0 to 10.0%

%

H/C Models Only,

On/Off Mode

HYS.H Hysteresis High

GEU (0.0 to 10.0% of sensor range)

GEU

Relay Cutoff,

ON/OFF Mode

HYS.L

Hysteresis Low

GEU (0.0 to 10.0% of sensor range)

GEU

Relay Activation,

ON/OFF Mode

HYS

Hysteresis

100.0%

0%

H/C:100.0%

0.0%

2 sec

0.0%

0.5%

GEU (0.5%)

HYS.H

ON

OFF

ON

On/Off Relay Behavior Based On Hysteresis Settings

Note: In H/C models, HYS.H and HYS.L replaced by HYS, and range high and low is 1/2 HYS setting

GEU (0.5%)

On

Off

po

poC

Output Group Parameter Summary

PD540 Series Nova Digital Process and Temperature Controller

Instruction Manual

21