Precision Digital PD540 User Manual

Page 7

Advertising
background image

1.1 SPECIFICATIONS

General

DISPLAY

Dual 4 digits, red LED, -1999 to 9999

DIN Sizes

PV Display

SP Display

Weight

mm (inch)

mm (inch)

g (oz)

1/16

11.3 (0.45)

9.5 (0.37)

198 (7.0)

3/16

14.0 (0.55)

12.0 (0.47)

324 (11.4)

1/8 (H)

19.8 (0.78)

11.5 (0.45)

306 (10.6)

1/8 (V)

13.6 (0.54)

10.5 (0.41)

304 (10.7)

1/4

20.5 (0.81)

11.0 (0.43)

389 (13.7)

FRONT PANEL

1/16 & 1/8 DIN: IP65; 3/16 & 1/4 DIN: IP55

SAMPLING TIME

250 ms

OVERRANGE

Over range PV reads ovR, under range PV reads -ovR

PROGRAMMING

Four front panel buttons and Modbus

METHODS

PID ZONES

3 programmable PID zone ranges, 1 PID PV deviation zone

NOISE FILTER

Programmable from 1 to 120

CALIBRATION

All ranges are calibrated at the factory

PASSWORD

Programmable password restricts modification of
programmed settings

POWER

100-240 VAC, 50/60 HZ, 10 W atts

FUSE

Required fuse: UL Recognized, 1 A, 250 V, slow blow

ISOLATION

2300 V input-to-output-to-power line;
4 kV relay output-to-input/output/power line

NUMBER OF

4 programmable set points

SET POINTS

ENVIRONMENTAL

Operating temperature range: 10ºC to 50ºC (50ºF to 110ºF)
Relative humidity: 20 to 90% non-condensing

MOUNTING

1/16, 3/16, 1/8, or 1/4 DIN size cutout required
Two panel mounting bracket assemblies provided
One one-piece bracket provided for the PD540

WARRA NTY

Three years parts and labor

Except where noted all specifications apply to operation at 23ºC.

PD540 Series Nova Digital Process and Temperature Controller

Instruction Manual

7

Advertising