- 16 -

5-2 AC OUTPUT MEASURING








Use a circuit above for measuring AC output.

A hot plate or lamp with a power factor of 1.0
may be used as a load. Adjust the load and rpm.
and check that the voltage range is as specified
in the following table at the rated amperage and
rated rpm.


5-3 MEASURING INSULATION RESISTANCE
Use a megger tester to check the insulation
resistance. Remove the control panel, and
disconnect the connector of GREEN lead for
ground. Connect a megger tester to one of
receptacle output terminals and the ground
terminal, then measure the insulation resistance.












Rated voltage

240V-60Hz

SGX3500

239-249

SGX5000

239-249

SGX7500

239-249

V

o

lt

ag

e

r

an

ge

model