Checking functional members – Subaru Robin SGX3500 User Manual

Page 20

Advertising
background image

- 18 -

6. CHECKING FUNCTIONAL MEMBERS

6-1 RECEPTACLES

Using a circuit tester, check continuity between
the two terminals at the rear of the receptacles
while the receptacle is mounted on the control
panel.
When continuity is found between the output
terminals of the receptacle with a wire connected
across these terminals, the receptacle is normal.
When the wire is removed and no continuity is
found between these terminals, the receptacles
are also normal.









6-2 CIRCUIT BREAKER
Check continuity between each of two
terminals at the rear of the circuit breaker
while it is mounted on the control panel.
Normally, there is continuity between each of
the two when the circuit breaker is on while
there is no continuity when the circuit breaker
is off.










CIRCUIT TESTER

(Continuity test)

PUSH Type

LEVER Type

AC CIRCUI BREAKER (Type 1)

AC CIRCUI BREAKER (Type 2)

Max voltage

AC CIRCUIT BREAKER

Frequency

Rated output

SGX5000
SGX7500

60Hz

SGX3500

3200VA

6700VA

4500VA

Rated fault current

18.75A

25A

37.5A

250V
250V
250V

SGX7500

6700VA

125V

20A

60Hz

Rated fault current

AC CIRCUIT BREAKER

Frequency

Rated output

Rated voltage