8. TROUBLESHOOTING

8-1 NO AC OUTPUT

8-1-1 CHECKING STATOR

(1) Remove control panel and disconnect stator wires at the connectors.

(2) Measure the resistance between terminals

on stator leads.

Refer to Table of Section 6-3 STATOR for

normal resistance.

If stator is faulty, replace it with a new one.




(3) Check the insulation resistance between

stator core and each stator lead using a

megger tester.

If insulation is bad, replace stator with a

new one.


8-1-2 CHECKING ROTOR

1) Field coil

Remove the brush holder and measure

resistance between the slip rings. Refer to

Section 6-4 ROTOR ASSEMBLY for normal

Resistance


NOTE : If the circuit tester is not sufficiently

accurate, it may not show the values
given and may give erroneous readings.
Erroneous reading will also occur when
there is a wide variation of resistance
among coil windings or when
measurement is performed at ambient
temperatures different from from 20°C
(68°F).