All installations and services must be performed by qualified service personnel.

25

b. The bottom edge of the vent termination elbow must be installed at

least 12-inches above the outlet of intake termination elbow.

c. The horizontal distance between the inlet and exhaust terminations

should be minimized, when possible, and should never exceed 24-
inches.

d. The vent and intake systems should utilize the same numbers of

elbows and approximately the same length of straight pipe to reach the
outside termination.

Figure 8: Typical Relative Locations of Direct Vent Terminations When

Sidewall Venting

3. Exhaust Vent Terminal Location Clearance Requirements

a. The vent terminal shall be located at least 3-feet above any forced air

inlet located within 10-feet. Refer to Figure 9 for a depiction of the
minimum required clearances between vent terminations and building
features according to the National Fuel Gas Code (NFGC).

b. The vent terminal shall be at least 12-inches below, 12-inches

horizontally from, or 12-inches above, any door, window, or gravity air
inlet into a building. The bottom of the vent terminal shall be located at
least 12-inches above grade.

c. The vent terminal shall not be located:

over public walkways or over an area where wetting of surfaces by

condensate, or water vapor, could create a nuisance or hazard,

near soffit vents, crawl space vents, or other areas where

condensate or water vapor could create a nuisance, hazard, or
cause property damage, and