Speed tap \ static pressure – Thermo Pride Gas/Propane Furnace Mobile Home CMC1 User Manual

Page 38

Advertising
background image

All installations and services must be performed by qualified service personnel.

36

CMC1-50D36

ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE

COOLING UNIT

HTG Speed

Recommended CLG Speed

24,000

LOW

MED-LOW

30,000

LOW

MED-HIGH

36,000

LOW

HIGH















































Speed Tap \
Static
Pressure

Furnace Airflow (CFM) vs. External Static pressure (in. WC.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Low

836

805

773

743

695

620

566

ML

1044

1010

972

914

860

826

752

MH

1250

1196

1146

1101

1038

977

902

High

1339

1338

1283

1233

1162

1086

1008

Speed Tap \
Static
Pressure

Temperature Rise vs. External Static Pressure (in. WC.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Low

53

55

57

59

63

71

78

ML

42

44

45

48

51

53

59

MH

35

37

38

40

42

45

49

High

31

33

34

36

38

41

44

Speed Tap
\ Static
Pressure

Blower Motor Current Draw (Amps) vs. External Static pressure (in. WC.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Low

3.3

3.2

3.1

3.0

2.9

2.7

2.6

ML

4.0

3.8

3.6

3.5

3.4

3.2

3.1

MH

4.6

4.4

4.2

4.1

4.0

3.8

3.6

High

5.3

5.1

5.0

4.9

4.7

4.6

4.4

Speed Tap \
Static
Pressure

Blower Motor Watts vs. External Static pressure (in. WC.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Low

315

311

304

300

292

281

275

ML

400

390

376

363

351

342

330

MH

485

467

452

441

427

412

394

High

573

555

544

530

513

493

477

=

Recommended operation range