Cmc1-50dv3, Speed tap \ static pressure – Thermo Pride Gas/Propane Furnace Mobile Home CMC1 User Manual

Page 40

Advertising
background image

All installations and services must be performed by qualified service personnel.

38

CMC1-50DV3

ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE

COOLING UNIT

HTG Speed

Recommended CLG Speed

24,000

LOW

MED-LOW

30,000

LOW

MED-HIGH

36,000

LOW

HIGH


Speed Tap \
Static
Pressure

Furnace Airflow (CFM) vs. External Static pressure (in. WC.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Low

700

639

567

497

437

387

332

ML

876

834

781

725

653

602

556

MED

990

948

907

857

811

756

700

MH

1174

1145

1107

1066

1026

987

942

High

1398

1365

1326

1299

1265

1252

1190




























Speed Tap \
Static
Pressure

Temperature Rise vs. External Static Pressure (in. WC.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Low

63

69

78

88

101

114

132

ML

50

53

56

61

67

73

79

MED

44

46

48

51

54

58

63

MH

37

38

40

41

43

45

47

High

31

32

33

34

35

35

37

Speed Tap
\ Static
Pressure

Blower Motor Current Draw (Amps) vs. External Static pressure (in. WC.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Low

1.1

1.1

1.2

1.2

1.2

1.3

1.4

ML

1.7

1.7

1.8

1.8

1.9

1.9

2.0

MED

2.2

2.2

2.3

2.4

2.5

2.5

2.5

MH

3.4

3.4

3.4

3.5

3.6

3.6

3.7

High

5.2

5.2

5.2

5.3

5.3

5.4

5.5

Speed Tap \
Static
Pressure

Blower Motor Watts vs. External Static pressure (in. WC.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Low

72

77

81

84

87

91

95

ML

123

127

133

137

141

145

148

MED

168

173

178

183

188

192

197

MH

266

272

277

284

290

296

301

High

438

442

445

450

455

461

468

=

Recommended operation range