All installations and services must be performed by qualified service personnel.

42

MAIN

BURNER

OPERATION

END

OF CYCLE

CALL

FOR

HEAT

SATISFIED

AFTER DELAY-TO-FAN-ON

PERIOD ENDS, CIRCULATING

AIR FAN IS ENERGIZED AT

HEATING SPEED. THE (OPTIONAL)

ELECTRONIC AIR CLEANER

AND HUMIDIFIER ARE

ENERGIZED.

AFTER THE DELAY-TO-

FAN-OFF PERIOD ENDS,

THE CIRCULATING AIR

FAN AND (OPTIONAL)

ELECTRONIC AIR CLEANER

ARE DE-ENERGIZED.

THE RETRY SEQUENCE

PROVIDES A 60 SECOND

WAIT BEFORE IGNITION

RETRY. RETRY IS

ATTEMPTED WITH AN

ADDITIONAL 10 SECONDS

OF IGNITOR WARM-UP

TIME.

WHEN THERMOSTAT IS

SATISFIED, CONTACTS

OPEN AND THE GAS

VALVE IS DE-ENERGIZED.

AFTER PROOF OF FLAME

LOSS, INDUCER STARTS 5 SECOND

POST SURGE AND (OPTIONAL)

HUMIDIFIER ARE

DE-ENERGIZED. THE DELAY-

TO-FAN-OFF PERIOD

BEGINS (120 SECONDS)

IF SYSTEM IS IN LOCKOUT, THE

MODULE WILL RESET ITSELF AFTER

60 MINUNTES OR MAY BE MANUALLY RESET BY

INTERRUPTING THE POWER TO THE

FURNACE AT THE DISCONNECT OR INTERRUPTING

THE CALL FOR HEAT AT THE THERMOSTAT.

IF THIS DOES NOT RESTART THE SYSTEM,

REFER TO THE TROUBLESHOOTING

SECTION OF THIS MANUAL.

IF IGNITION ATTEMPT IS

UNSUCCESSFUL, ONE MORE

RETRY WILL BE MADE

BEFORE THE CONTROL BOARD

GOES INTO SYSTEM LOCKOUT.

IF FLAME IS DETECTED,

THEN LOST, THE CONTROL BOARD

WILL REPEAT THE INITIAL IGNITION

SEQUENCE FOR A TOTAL OF SIX

RECYCLES. AFTER SIX UNSUCCESSFUL

RECYCLE ATTEMPTS, THE CONTROL

WILL GO INTO SYSTEM LOCKOUT.