Thermo Pride Premiere XT 16 SEER User Manual

Page 21

Advertising
background image

21

SECTION X: INSTRUCTING THE OWNER

Assist owner with processing warranty cards and/or online registration.

Review Owners Guide and provide a copy to the owner and guidance

on proper operation and maintenance. Instruct the owner or the opera-

tor how to start, stop and adjust temperature setting.
When applicable, instruct the owner that the compressor is equipped

with a crankcase heater to prevent the migration of refrigerant to the

compressor during the “OFF” cycle. The heater is energized only when

the unit is not running. If the main switch is disconnected for long peri-

ods of shut down, do not attempt to start the unit until 8 hours after the

switch has been connected. This will allow sufficient time for all liquid

refrigerant to be driven out of the compressor.
The installer should also instruct the owner on proper operation and

maintenance of all other system components.

MAINTENANCE

1. Dirt should not be allowed to accumulate on the outdoor coils or

other parts in the air circuit. Clean as often as necessary to keep the

unit clean. Use a brush, vacuum cleaner attachment, or other suit-

able means.

2. The outdoor fan motor is permanently lubricated and does not

require periodic oiling.

3. If the coil needs to be cleaned, it should be washed with Calgon

Coilclean (mix one part Coilclean to seven parts water). Allow solu-

tion to remain on coil for 30 minutes before rinsing with clean water.

Solution should not be permitted to come in contact with painted

surfaces.

4. Refer to the furnace or air handler instructions for filter and blower

motor maintenance.

5. The indoor coil and drain pan should be inspected and cleaned reg-

ularly to prevent odors and assure proper drainage.

IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS-
CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR,
SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS
UNIT.

TABLE 2: R-410A Saturation Properties

TEMP. °F

PRESSURE

PSIG

TEMP. °F

PRESSURE

PSIG

TEMP. °F

PRESSURE

PSIG

TEMP. °F

PRESSURE

PSIG

TEMP. °F

PRESSURE

PSIG

45

129.70

60

169.60

75

217.40

90

274.10

105

340.50

46

132.20

61

172.60

76

220.90

91

278.20

106

345.30

47

134.60

62

175.50

77

224.40

92

282.30

107

350.10

48

137.10

63

178.50

78

228.00

93

286.50

108

355.00

49

139.60

64

181.60

79

231.60

94

290.80

109

360.00

50

142.20

65

184.60

80

235.30

95

295.10

110

365.00

51

144.80

66

187.70

81

239.00

96

299.40

111

370.00

52

147.40

67

190.90

82

242.70

97

303.80

112

375.10

53

150.10

68

194.10

83

246.50

98

308.20

113

380.20

54

152.80

69

197.30

84

250.30

99

312.70

114

385.40

55

155.50

70

200.60

85

254.10

100

317.20

115

390.70

56

158.20

71

203.90

86

258.00

101

321.80

116

396.00

57

161.00

72

207.20

87

262.00

102

326.40

117

401.30

58

163.90

73

210.60

88

266.00

103

331.00

118

406.70

59

166.70

74

214.00

89

270.00

104

335.70

119

412.20

Advertising