Notice – Thermo Pride Premiere XT 16 SEER User Manual

Page 3

Advertising
background image

3

GROUND INSTALLATION

The unit may be installed at ground level on a solid base that will not

shift or settle, causing strain on the refrigerant lines and possible leaks.

Maintain the clearances shown in Figure 1 and install the unit in a level

position.
Normal operating sound levels may be objectionable if the unit is placed

directly under windows of certain rooms (bedrooms, study, etc.).
Condensate will drain from beneath the coil of the outdoor unit during

the defrost cycle. Normally this condensate may be allowed to drain

directly on the ground.

Elevate the unit sufficiently to prevent any blockage of the air entrances

by snow in areas where there will be snow accumulation. Check the

local weather bureau for the expected snow accumulation in your area.
Isolate the unit from rain gutters to avoid any possible wash out of the

foundation.

ROOF INSTALLATION

When installing units on a roof, the structure must be capable of sup-

porting the total weight of the unit, including a pad, lintels, rails, etc.,

which should be used to minimize the transmission of sound or vibra-

tion into the conditioned space.

UNIT PLACEMENT

1. Provide a base in the pre-determined location.
2. Remove the shipping carton and inspect for possible damage.
3. Compressor tie-down bolts should remain tightened.
4. Position the unit on the base provided.

LIQUID LINE FILTER-DRIER

The heat pumps have a solid core bi-flow filter/dryer located on the liq-

uid line.

PIPING CONNECTIONS

The outdoor unit must be connected to the indoor coil using field sup-

plied refrigerant grade copper tubing that is internally clean and dry.

Units should be installed only with the tubing sizes for approved system

combinations as specified in Tabular Data Sheet. The charge given is

applicable for total tubing lengths up to 15 feet. See Application Data

Part Number 247077 for installing tubing of longer lengths and elevation

differences.

PRECAUTIONS DURING LINE INSTALLATION

1. Install the lines with as few bends as possible. Care must be taken

not to damage the couplings or kink the tubing. Use clean hard

drawn copper tubing where no appreciable amount of bending

around obstruction is necessary. If soft copper must be used, care

must be taken to avoid sharp bends which may cause a restriction.

2. The lines should be installed so that they will not obstruct service

access to the coil, air handling system or filter.

3. Care must also be taken to isolate the refrigerant lines to minimize

noise transmission from the equipment to the structure.

4. The vapor line must be insulated with a minimum of 1/2" foam rub-

ber insulation (Armaflex or equivalent). Liquid lines that will be

exposed to direct sunlight and/or high temperatures must also be

insulated.

5. Tape and suspend the refrigerant lines as shown. DO NOT allow

tube metal-to-metal contact. See Figure 2.

6. Use PVC piping as a conduit for all underground installations as

shown in Figure 3. Buried lines should be kept as short as possible

to minimize the build up of liquid refrigerant in the vapor line during

long periods of shutdown

7. Pack fiberglass insulation and a sealing material such as permagum

around refrigerant lines where they penetrate a wall to reduce vibra-

tion and to retain some flexibility.

8. See Form 247077 for additional piping information.

The outdoor unit should not be installed in an area where mud or ice
could cause personal injury. Remember that condensate will drip from
the unit coil during heat and defrost cycles and that this condensate
will freeze when the temperature of the outdoor air is below 32°F.

Heat pumps will defrost periodically resulting in water drainage. The
unit should not be located where water drainage may freeze and cre-
ate a hazardous condition - such as sidewalks and steps.

Replacements for the liquid line drier must be exactly the same as
marked on the original factory drier. See Source 1 for O.E.M. replace-
ment driers.

Failure to do so or using a substitute drier or a granular type may
result in damage to the equipment.

Filter-Drier

Source 1 Part No.

Apply with Models

S1-52636219000

All Sizes

NOTICE

NOTICE

This system uses R-410A refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.
Gauge sets, hoses, refrigerant containers, and recovery system must
be designed to handle R-410A. If you are unsure, consult the equip-
ment manufacturer.

Never install a suction-line filter drier in the liquid line of an R-410A
system. Failure to follow this warning can cause a fire, injury or death.

Using a larger than specified line size could result in oil return prob-
lems. Using too small a line will result in loss of capacity and other
problems caused by insufficient refrigerant flow. Slope horizontal
vapor lines at least 1" every 20 feet toward the outdoor unit to facili-
tate proper oil return.

FIGURE 2: Tubing Hanger

NOTICE

Liquid
Line

Incorrect

Correct

Tape

Sheet Metal Hanger

Insulated Vapor Line

Advertising