Notice – Thermo Pride Premiere XT 16 SEER User Manual

Page 7

Advertising
background image

7

SECTION VIII: ELECTRICAL

CONNECTIONS

GENERAL INFORMATION & GROUNDING

Check the electrical supply to be sure that it meets the values specified

on the unit nameplate and wiring label.
Power wiring, control (low voltage) wiring, disconnect switches and over

current protection must be supplied by the installer. Wire size should be

sized per NEC requirements.

The complete connection diagram and schematic wiring label is located

on the inside surface of the unit service access panel and this instruc-

tion.

FIELD CONNECTIONS POWER WIRING

1. Install the proper size weatherproof disconnect switch outdoors and

within sight of the unit.

2. Remove the screws at the bottom of the corner cover. Slide corner

cover down and remove from unit. See Figure 6.

3. Run power wiring from the disconnect switch to the unit.
4. Remove the service access panel to gain access to the unit wiring.

Route wires from disconnect through power wiring opening provided

and into the unit control box.

5. Install the proper size time-delay fuses or circuit breaker, and make

the power supply connections.

6. Energize the crankcase heater if equipped to save time by preheat-

ing the compressor oil while the remaining installation is completed.

FIELD CONNECTIONS CONTROL WIRING -

CONVENTIONAL

1. Route low voltage wiring into bottom of control box as shown in Fig-

ure 6. Make low voltage wiring connections inside the junction box

per Figures 10 - 15.

2. The complete connection diagram and schematic wiring label is

located on the inside surface of the unit service access panel.

3. Replace the corner cover and service access panel removed in

Steps 2 and 4 of the “Field Connections Power Wiring” section.

4. All field wiring to be in accordance with national electrical codes

(NEC) and/or local-city codes.

5. Mount the thermostat about 5 ft. above the floor, where it will be

exposed to normal room air circulation. Do not place it on an outside

wall or where it is exposed to the radiant effect from exposed glass

or appliances, drafts from outside doors or supply air grilles.

6. Route the 24-volt control wiring (NEC Class 2) from the outdoor unit

to the indoor unit and thermostat.

FIELD CONNECTIONS CONTROL WIRING -

COMMUNICATING

1. The Communication Harness is provided with the communicating

thermostat.

2. Route low voltage four conductor shielded thermostat communica-

tions harness into junction box and connect to communications port

on control board. See Figure 6.

3. The complete connection diagram and schematic wiring label is

located on the inside surface of the unit service access panel.

All field wiring must USE COPPER CONDUCTORS ONLY and be in
accordance with Local, National Fire, Safety & Electrical Codes. This
unit must be grounded with a separate ground wire in accordance
with the above codes.

FIGURE 6: Typical Field Wiring

Corner
Cover

Control
Wiring

Power
Wiring

Service
Access

Panel

Ambient
Temperature
Sensor

Ambient temperature sensor should extend below corner cover by 1”.

To eliminate erratic operation, seal the hole in the wall at the thermo-
stat with permagum or equivalent to prevent air drafts affecting the
operation of in the thermostat.

If unit is going to be setup as a communicating system, the conven-
tional wiring must be removed from the Outdoor Control Board.

FIGURE 7: Communications Harness Connection

NOTICE

NOTICE

COMMUNICATIONS PORT

CONTROL BOARD

COMMUNICATIONS
HARNESS

JUNCTION
BOX

Advertising