Figure 3 – Emerson Series 610 User Manual

Page 19

Advertising
background image

Configuring Your Neutral and Ground Connections

15

6.3

Preferred Grounding Configuration With Isolated Bypass

Another configuration in this power range is the Single-Module System with 480 or 600 VAC input,

208 VAC output, a Bypass Isolation Transformer and a connected load consisting of multiple distribu-

tion panelboards or switchboards. Figure 3 shows a typical installation.
The Bypass Transformer provides isolation and may step down the voltage to the bypass input. The

Bypass Transformer and the UPS module together constitute a separately derived system, since there

is no direct electrical connection between the input (service entrance) circuit conductors and the out-

put circuit conductors.

The bonding of the neutral to the grounding conductor can theoretically be done at either the UPS

module or the Bypass Transformer. However, we recommend bonding at the Bypass Transformer

because the UPS module will sometimes be powered down for maintenance and its output trans-

former will be out of the circuit. The neutral should be bonded to ground and a local grounding elec-

trode should be installed at the Bypass Transformer, per NEC 250-30.

Figure 3

Preferred grounding configuration with isolated bypass

Features of this configuration include:

• The UPS receives its bypass neutral from the Bypass Transformer
• The output is isolated from the input circuit conductors, and
• Some amount of common-mode noise attenuation can be obtained for sensitive loads if the

UPS module and Bypass Transformer are located close to sensitive loads.

NOTE
Figure 3
shows a wye-connected source, but the same grounding scheme would apply for a

delta source at the service entrance.

GROUNDING
ELECTRODE
PER NEC 250-24

LOCAL GROUNDING
ELECTRODE
PER NEC 250-30

Advertising