2 control wiring, 3 battery wiring, Control wiring – Emerson Series 610 User Manual

Page 27: Battery wiring, Warning, Caution

Advertising
background image

Wiring Considerations

23

7.2

Control Wiring

Control wiring must be flexible stranded, tinned copper and run in individual separate steel conduits.

Control wiring must be separated from power wiring. In addition, each control wiring cable group

should be run in a separate conduit to minimize control signal interference.
If your system has any installed options, special wire lists will be included in your Submittal Drawing

Package. Contact your Liebert Sales Representative for assistance if the submittal drawings have

been lost or misplaced.
All control cable groups are connected to different Interface Modules (IFMs) and/or terminal blocks

inside the UPS. Figure 14 shows the typical location of each IFM inside the UPS. The position of a

particular IFM may be different for your UPS, depending on the model and the installed options.

7.3

Battery Wiring

Power wiring to the battery cabinet connects positive, negative, and ground power cables from the

battery cabinet to the associated UPS. Connection of the UPS to the battery cabinet serves to both

charge and discharge the batteries (when needed). The battery disconnect (circuit breaker) requires a

control cable. Except for interconnect wiring between multiple battery cabinets, power and control

cables are field supplied. Refer to Battery Cabinet submittal drawings.

Call Liebert Global Services to schedule installation check-out, final battery intercell connections and

start-up.

NOTE
The UPS control and communication wiring are considered Class 2 circuits by NEC

standards. However, NEC Class 1 wiring methods are required for these circuits to ensure

proper operation of the UPS.

!

WARNING

A battery intercell connection on each tier of the Liebert battery cabinet is disconnected for

safety during shipment. Do not complete these connections. A Liebert Global Services

representative will complete these connections as part of start-up. An improperly installed

unit can result in injury to personnel or damage to equipment.

!

CAUTION

Be sure polarity is correct when wiring the battery cabinet to the connected equipment

(positive to positive; negative to negative). If polarity is not correct, fuse failures or equipment

damage can result.

!

CAUTION

Cables between batteries and the UPS should be run in matched pairs,

positive-with-negative, within each conduit or cable run. Grouping

like-polarity cables together (i.e., positive-with-positive and

negative-with-negative) can cause stress or damage to the cables,

conduit or buswork.

NOTE
A Liebert Battery Specialist can perform a detailed inspection of the entire battery system to

ensure it meets current IEEE standards. This inspection service is recommended because

batteries are a very critical part of the UPS system.

Advertising