Wiring Considerations

19

7.0

W

IRING

C

ONSIDERATIONS

Refer to Appendix A and drawings in 10.0 - Installation Drawings. Determine AC currents for

your system (kVA, voltage and options). Also refer to the equipment nameplate for the model number,

rating and voltage. For wire termination data, refer to Tables 2 through 4.

!

WARNING

All power connections must be completed by a licensed electrician experienced in wiring this

type of equipment. Wiring must be installed in accordance with all applicable national and

local electrical codes. Improper wiring may cause damage to the equipment or injury to

personnel.
Verify that all incoming high and low voltage power circuits are de-energized and locked out

before installing cables or making any electrical connections.

NOTE
Use 75°C copper wire. Select wire size based on the ampacities in Table 5 of this manual, a

reprint of Table 310-16 and associated notes of the National Electrical Code (NFPA 70).

!

CAUTION

The weight of power cables must be adequately supported to avoid stress on busbars and lugs.

In addition to weight support, the following restraining method is recommended to control

cable movement during external fault conditions:
• Wrap line cables together at 6 and 12 in. (152 and 305mm) from the terminals with five

wraps of 3/8 in. (9.5mm) nylon rope or equivalent (tensile strength of 2000 lbs.; 907kg).

• Support the remainder of the cable with five wraps every 6 in. (152mm) or one wrap every

1 in. (25mm).